Transformers reduce the voltage of the electricity supplied by the utility to a level suitable for use by the electric equipment. Since all of the electricity used by a company passes through a transformer, even a small efficiency improvement will result in significant electricity savings. High-efficiency transformers are now available that can reduce total electricity use by approximately 1 percent. Reduced electricity use provides cost savings for a company.

Two types of energy losses occur in transformers: load and no-load losses.

Load losses: result from resistance in the copper or aluminum windings. Load losses (also called winding losses) vary with the square of the electrical current (or load) flowing through the windings. At low loads (e.g. under 30 percent loading), core losses account for the majority of losses, but as the load increases, winding losses quickly dominate and account for 50 to 90 percent of transformer losses at full load. Winding losses can be reduced through improved conductor design, including proper materials selection and increases in the amount of copper conductor employed.

No-load losses: result from resistance in the transformer's laminated steel core. These losses (also called core losses) occur whenever a transformer is energized and remain essentially constant regardless of how much electric power is flowing through it. To reduce core losses, high-efficiency transformers are designed with a better grade of core steel and with thinner core laminations than standard-efficiency models.

Total transformer losses are a combination of the core and winding losses. Unfortunately, some efforts to reduce winding losses increase core losses and vice versa. For example, increasing the amount of conductor used reduces the winding losses, but it may necessitate using a larger core, which would increase core losses. Manufacturers are developing techniques that optimize these losses based on the expected loading.

Annual energy losses and cost of these losses:
The annual energy losses of a transformer can be estimated from the following formula
Wloss = 8760(Po+Pk L2)
Where,
Wloss - is the annual energy loss in kWh.
Po - is the no-load loss in kW.
Pk - is the short-circuit loss (or load loss) in kW.
L - is the average per-unit load on the transformer.
8760 - is the number of hours in a year.

To calculate the cost of these losses, they need to be converted to the moment of purchase by assigning capital values, to be able to put them into the same perspective as the purchase price. This is called the Total Capitalized Cost of the losses, TCC loss. This can be calculated using the following formula
TCCloss=8760Wloss(1+i)n1i(1+i)nC
Where,
C - is the estimated average cost per kWh in each year.
i - is the estimated interest rate.
n - is the expected life time of the transformer.

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...