Skip to main content

STEPS TO BETTER MOTOR APPLICATIONS

1) KNOW THE LOAD CHARACTERISTICS
For line-operated motors, loads fall into three general categories: constant torque, torque that changes abruptly, and torque that change gradually over time.

Bulk material conveyors, extruders, positive displacement pumps, and compressors without air unloaders run at relatively steady levels of torque. Sizing a motor for these applications is simple once the torque (or horsepower) for the application is known. Load demands by elevators, compactors, punch presses, saws, and batch conveyors change abruptly from low to high in a short time, often in a fraction of a second. The most critical consideration for selecting a motor in these cases is to choose one whose speed-torque curve exceeds the load torque curve.

Loads from centrifugal pumps, fans, blowers, compressors with unloaders, and similar equipment tend to be variable over time. In choosing a motor for these conditions, consider the highest continuous load point, which typically occurs at the highest speed.

2) GET A HANDLE ON HORSEPOWER
The rule of thumb for motor horsepower is: Select only what you need, and avoid the temptation to oversize or undersize. Calculate the required horsepower from this formula:
Horsepower = Torque x Speed / 5250
Where torque is in lb-ft and speed is in rpm.
3) GETTING STARTED
Another consideration is inertia, particularly during startup. Every load represents some value of inertia, but punch presses, ball mills, crushers, gearboxes that drive large rolls, and certain types of pumps require high starting torques due to the huge mass of the rotating elements. Motors for these applications need to have special ratings so that the temperature rise at startup does not exceed the allowable temperature limit. A properly sized motor must be able to turn the load from a dead stop (locked-rotor torque), pull it upto operating speed (pull-up torque), and then maintain the operating speed. Motors are rated as one of four “design types” for their ability to endure the heat of that starting and pull up. In ascending order of their ability to start inertial loads, NEMA designates these as design type A, B, C, and D. Type B is the industry standard and is a good choice for most commercial and industrial applications.

4) ADJUST FOR DUTY CYCLE
Duty cycle is the load that a motor must handle over the period when it starts, runs, and stops.

Continuous duty: is—by far—the simplest and most efficient application. The duty cycle begins with startup, then long periods of steady operation where the heat in the motor can stabilize as it runs. A motor in continuous duty can be operated safely at or near its rated capacity because the temperature has a chance to stabilize.

Intermittent duty: is more complicated. The life of commercial airplanes is measured by their number of landings; in the same way, the life of a motor is proportional to the number of starts it makes. Frequent starts shorten life because inrush current at startup heats the conductor rapidly. Because of this heat, motors have a limited number of starts and stops that they can make in an hour.

5) THE LAST CONSIDERATION, MOTOR HYPOXIA
If your motor is going to operate at altitudes that are substantially above sea level, then it will be unable to operate at its full service factor because, at altitude, air is less dense and does not cool as well. Thus, for the motor to stay within safe limits of temperature rise, it must be derated on a sliding scale. Up to an altitude of 3,300 ft, SF = 1.15; at 9000 ft, it declines to 1.00. This is an important consideration for mining elevators, conveyors, blowers, and other equipment that operates at high altitudes.

Comments

Popular posts from this blog

AUTO TRANSFORMER TAP CHANGING

Figure shows diagrammatically auto-transformer tap changing. Here, a mid-tapped auto-transformer or reactor is used. One of the lines is connected to its mid-tapping. One end, say a of this transformer is connected to a series of switches across the odd tappings and the other end b is connected to switches across even tappings. A short-circuiting switch S is connected across the auto-transformer and remains in the closed position under normal operation. In the normal operation, there is no inductive voltage drop across the auto-transformer. Referring to Figure, it is clear that with switch 5 closed, minimum secondary turns are in the circuit and hence the output voltage will be the lowest. On the other hand, the output voltage will be maximum when switch 1 is closed. Suppose now it is desired to alter the tapping point from position 5 to position 4 in order to raise the output voltage. For this purpose, short-circuiting switch S is opened, switch 4 is closed, then switch 5 is op...

COMPONENTS OF HIGH VOLTAGE DC TRANSMISSION SYSTEM

Figure: A schematic of a bipolar HVDC system identifying main components

PLUG REVERSING OF CAPACITOR START MOTORS

The capacitor start motors suffer from the disadvantage that they are not easily reversible due to the centrifugal switch connected in the auxiliary winding. The motor cannot be instantaneously reversed by simple control as the auxiliary winding remains disconnected till the motor comes near to zero speed. However, by proper design of the control circuit the motor can be made instantly reversible. This is accomplished by using an electromagnetic relay along with a special two contact centrifugal switch as shown in Figure. The circuit shown in Figure is for a small hoist using a capacitor start motor. The upper and lower limits of travel are controlled by two limit switches viz. LSU and LSD. When UP-push button is pressed, contactor U gets energized. Its contacts U 1  and U 2  energies the main winding. Closing of its contact U 3  causes relay R to get energized through the centrifugal switch contacts A—B. After the energization of relay R auxiliary winding gets ene...

BENEFITS OF UTILIZING FACTS DEVICES

The advantages of using FACTS devices in electrical transmission systems are described below. 1. MORE UTILIZATION OF EXISTING TRANSMISSION SYSTEM In all the countries, the power demand is increasing day by day to transfer the electrical power and controlling the load flow of the transmission system is very necessary this can be achieved by more load centers which can change frequently. Addition of new transmission line is very costly to take the increased load on the system; in that case FACTS devices are much economical to meet the increased load on the same transmission lines. 2. MORE INCREASED TRANSIENT AND DYNAMIC STABILITY OF THE SYSTEM The Long transmission lines are inter-connected with grids to absorb the changing the loading of the transmission line and it is also seen that there should be no line fault creates in the line / transmission system. By doing this the power flow is reduced and transmission line can be trip. By the use of FACTS devices high power t...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...