Skip to main content

COMMUTATION

When the armature rotates a half a revolution ‘A’ is positioned at the south pole “S” and ‘B’ positioned at the north pole “N”. As the magnetic field surrounding ‘A’ is in the anti-clockwise direction the magnetic field would be stronger under ‘A’ and above ‘B’, which would mean that the armature would now rotate in the opposite direction. The motor would never rotate.

To maintain rotation of the armature in the one direction the flow or current through the armature must be reversed when ‘A’ is at the “S” pole of the field coil.

A commutator is used with the motor to reverse the current flowing in the armature. Fig. “X” shows the black half of the armature at “N” and is connected via the segment of the commutator through the carbon brush to the battery negative terminal. In this position, the current flow through the armature produces a magnetic field of anti-clockwise direction through the black half ‘A’ of the armature and clock-wise through the white ‘B’. Interaction occurs and the loop rotates.

Fig. ‘Y’, the armature has moved through half a turn so the white section is now at “N”. The brush which connects to the negative side of the battery is now in contact with the white segment of the commutator. The current flowing in the armature is now reversed which means the direction of the lines of force of white is now anticlockwise and clockwise in the black “A”.



The interaction of the magnetic fields will rotate the armature in the same direction as when black “A” was at “N”. As the armature rotates therefore the magnetic field of the armature remains constant to the main field.

To increase the power of the motor many wire coils or loops are used in the armature tc maintain a constant push on the armature. Four poles are used two north and two south to produce a strong main field and are wound to give alternate N and S poles. Because some starters use 200 amps when operating four carbon brushes are fitted to distribute the current load.

Starter motors are usually series-wound motors because they produce their maximum torque at the beginning of their armature rotation.

Comments

Popular posts from this blog

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

PRINCIPLE OF OPERATION OF UNIFIED POWER FLOW CONTROLLER UPFC

UPFC consist of two back to back converters named VSC1 and VSC2, are operated from a DC link provided by a dc storage capacitor. These arrangements operate as an ideal ac to ac converter in which the real power can freely flow either in direction between the ac terminals of the two converts and each converter can independently generate or absorb reactive power as its own ac output terminal. Figure: Basic UPFC scheme One VSC is connected to in shunt to the transmission line via a shunt transformer and other one is connected in series through a series transformer. The DC terminal of two VSCs is coupled and this creates a path for active power exchange between the converters. VSC provide the main function of UPFC by injecting a voltage with controllable magnitude and phase angle in series with the line via an injection transformer. This injected voltage act as a synchronous ac voltage source. The transmission line current flows through this voltage source resulting in reactive an...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

MESH TOPOLOGIES AND ITS ADVANTAGES AND DISADVANTAGES

A mesh topology is not very common in computer networking today. In a mesh topology, every workstation has a connection to every other component of the network, as illustrated in Figure. Figure: Mesh Topology ADVANTAGES OF MESH TOPOLOGY: The biggest advantage of a mesh topology is fault tolerance, meaning that, if there is a break in a cable segment, traffic can be rerouted through a different pathway because there are multiple pathways to send data from one system to another. This fault tolerance means that it is almost impossible for the network to go down due to a cable fault. DISADVANTAGES OF MESH TOPOLOGY: A disadvantage of a mesh topology is the cost of the additional cabling and network interfaces to create the multiple pathways between each system. A mesh topology is very hard to administer and manage because of the numerous connections.

CLASSIFICATION OF HVDC LINKS

HVDC links may be broadly classified into the following categories: Monopolar Links Bipolar Links Homopolar Links The basic configuration of a monopolar link is shown in figure. It uses one conductor, usually of negative polarity. The return path is provided by ground or water. Cost considerations often lead to the use of such systems, particularly for cable transmission. This type of configuration may also be the first stage in the development of a bipolar system. Instead of ground return, a metallic return may be used in situation where the earth resistivity is too high or possible interference with underground/ under water metallic structures is objectionable. The conductor forming the metallic return is at low voltage.