METHODS OF STARTING OF SYNCHRONOUS MOTOR

(1) By using a starting motor. This motor is directly coupled to the motor. It may be an induction motor which can run on a synchronous speed closer to the synchronous speed of the main motor.

(2) Starting as an induction motor. This is the most usual method in which the motor is provided with a special damper winding on rotor poles. The stator is switched on to supply either directly or by star delta/reduced voltage starting. When the rotor reaches more than 95% of the synchronous speed, the dc circuit breaker for field excitation is switched on and the field current is gradually increased. The rotor pulls into synchronism

(A) Pull-in torque. It is the maximum constant load torque under which the motor will pull into synchronism at the rated rotor supply voltage and rated frequency, when the rated field current is applied

(B) Nominal pull in torque. It is the value of pull in torque at 95 percent of, the synchronous speed with the rated voltage and frequency applied to the stator when the motor is running with the winding current.
(C) Pull out torque. It is the maximum sustained torque which the motor will develop at synchronous speed for I minute with rated frequency and with rated field current.

(D) Pull up torque. It is the minimum torque developed between standstill and .pull in point. This torque must exceed the load torque by sufficient margin to ensure satisfactory acceleration of the load during starting.

(E) Reluctance torque. It is fraction of the total torque with the motor operating synchronously. It results from saliency of the poles. It is approximately 30% of the pull-out torque.

(F) Locked rotor torque. It is the maximum torque which a synchronous motor will-develop at rest, for any angular positions of the rotor at the rated voltage and frequency.

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...