Skip to main content

WAYS TO MEASURE ELECTRICAL POWER SYSTEM RELIABILITY

Reliability of a system is difficult to measure. Perhaps the best way is through evaluation of the consequences of possible consumer interruptions. Investigations have shown that the best measure of reliability is that of consumer reaction.

Five conditions that have been identified impact the value an average consumer puts on an unsupplied megawatt-hour of lost energy:
  1. The activities affected by the curtailment and, therefore, the time of day and mix of customers
  2. The number of interruptions
  3. Availability of advance warning
  4. Weather conditions and, therefore, the time of year
  5. The duration of the interruption
Figure 9-1 shows that this reaction increases dramatically as the frequency of outages increase, as the duration of the outage increases, and with the magnitude or extent of the outage. The following function presents a means of evaluating this reaction:

R = function of {K, F, T, P, t}

Where K is an empirical coefficient proportional to the consumer’s dependence on electricity, F is the frequency of interruptions, T is equal to duration of the interruptions, P is the amount of load interrupted, and t is the time when the interruption occurs. Experience has shown that K increases with increasing consumption of electricity per customer, and t is greatest at the time of day, week, or year when people suffer the greatest hardships if service is interrupted. This criterion for reliability evaluation does not consider other curtailments of service, such as voltage or frequency reductions. These “partial” curtailments are not as important to most consumers as a complete interruption but they should also be considered.

Figure 9-1. NERC regions. Source: NERC.
A number of indices have been developed, primarily for the distribution system, to provide another measure of reliability:

SAIFI (System Average Interruption Frequency Index) measures the average frequency of sustained interruptions per customer

SAIDI (System Average Interruption Duration Index) measures the average time that all customers are interrupted

CAIDI (Customer Average Interruption Duration Index) represents the average time required to restore service to the average customer per sustained outage

MAIFI (Momentary Average Interruption Frequency Index) tracks the average frequency of momentary interruptions, typically defined as less than five minutes

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...