OPERATING CHARACTERISTICS OF SHUNT REACTOR

1) LINEARITY:

For normal operating voltages there is a linear relationship between applied voltage and reactor current (i.e. a small increase in voltage will result in a proportional increase in current). Magnetic fluxes and flux densities are also proportional to the time integral of the applied voltage. With a voltage of sinusoidal shape the fluxes and flux densities are also proportional to the voltage. The deviation from a true sinusoidal shape in line voltage is in general negligible for normal operating voltages.

As the magnetic flux to a great extent has its path in magnetic core steel the core steel will get saturated for flux densities above a certain level, the saturation point. Below and up to the saturation point only a small current is needed to magnetize the core steel and the extra current needed to reach a marginal increase flux density is small. Once above the saturation point the extra current needed to further increase the flux density will be large.

2) HARMONIC CONTENT:

Steady state harmonics in reactor current arise from partial saturation in the magnetic circuit. These effects are in fact very small, and without practical importance for relaying and communication interference. Of all harmonics the third harmonic will be dominant. In the reactor neutral the third harmonics in the three phases add together and act like a zero sequence current.

3) ASYMMETRY BETWEEN PHASES:

The tolerances on asymmetry between phases of a three-phase reactor or between single-phase units forming a three-phase bank can be judged by the amount of residual harmonics. The result is a zero sequence current in the neutral connection. Standards are realistic, but better tolerances are possible to achieve. A usual figure is 0.5 %.

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...