TESTING VOLTAGES

Power systems equipment must withstand not only the rated voltage (Vm), which corresponds to the highest voltage of a particular system, but also over voltages. Accordingly, it is necessary to test high voltages. Equipment during its development stage and prior to commissioning. The magnitude and type of test voltage varies with the rated voltage of a particular apparatus. The standard methods of measurement of high-voltage and the basic techniques for application to all types of apparatus for alternating voltages, direct voltages, switching impulse voltages and lightning impulse voltages are laid down in the relevant national and international standards.

Testing with power frequency voltages

To assess the ability of the apparatus’s insulation withstand under the system’s power frequency voltage the apparatus is subjected to the 1-minute test under 50 Hz or 60 Hz depending upon the country. The test voltage is set at a level higher than the expected working voltage in order to be able to simulate the stresses likely to be encountered over the years of service. For indoor installations the equipment tests are carried out under dry conditions only. For outdoor equipment tests may be required under conditions of standard rain as prescribed in the appropriate standards.

Testing with lightning impulse voltages

Lightning strokes terminating on transmission lines will induce steep rising voltages in the line and set up travelling waves along the line and may damage the system’s insulation. The magnitude of these over voltages may reach several thousand kilo volts, depending upon the insulation. Exhaustive measurements and long experience have shown that lightning over voltages are characterized by short front duration, ranging from a fraction of a microsecond to several tens of microseconds and then slowly decreasing to zero. The standard impulse voltage has been accepted as a periodic impulse that reaches its peak value in 1.2 /sec and then decreases slowly (in about 50 /sec) to half its peak value. In addition to testing equipment, impulse voltages are extensively used in research laboratories in the fundamental studies of electrical discharge mechanisms, notably when the time to breakdown is of interest.

Testing with switching impulses

Transient over voltages accompanying sudden changes in the state of power systems, e.g. switching operations or faults, are known as switching impulse voltages. It has become generally recognized that switching impulse voltages are usually the dominant factor affecting the design of insulation in high voltage. power systems for rated voltages of about 300 kV and above. Accordingly, the various international standards recommend that equipment designed for voltages above 300 kV be tested for switching impulses. Although the wave shape of switching over voltages occurring in the system may vary widely, experience has shown that for flashover distances in atmospheric air of practical interest the lowest withstand values are obtained with surges with front times between 100 and 300 /sec. Hence, the recommended switching surge voltage has been designated to have a front time of about 250 /sec and half value time of 2500 /sec. For GIS (gas-insulated switchgear) on-site testing, oscillating switching impulse voltages are recommended for obtaining higher efficiency of the impulse voltage generator.

D.C. voltages

In the past dc voltages have been chiefly used for purely scientific research work. Industrial applications were mainly limited to testing cables with relatively large capacitance, which take a very large current when tested with ac voltages, and in testing insulations in which internal discharges may lead to degradation of the insulation under testing conditions. In recent years, with the rapidly growing interest in HVDC transmission, an increasing number of industrial laboratories are being equipped with sources for producing dc high voltages. Because of the diversity in the application of dc high voltages, ranging from basic physics experiments to industrial applications, the requirements on the output voltage will vary accordingly.

Testing with very low-frequency voltage

In the earlier years when electric power distribution systems used mainly paper-insulated lead covered cables (PILC) on-site testing specifications called for tests under dc voltages. Typically the tests were carried out at 4–4.5V0.

The tests helped to isolate defective cables without further damaging good cable insulation. With the widespread use of extruded insulation cables of higher dielectric strength, the test voltage levels were increased to 5–8V0. In the 1970s premature failures of extruded dielectric cables factory tested under dc voltage at specified levels were noted. Hence on-site testing of cables under very low frequency (VLF) of approximately 0.1Hz has been adopted.

Comments

Popular posts from this blog

Auto Transformer Tap Changing

Auto Transformer Tap Changing: Working Principle, Switching Sequence and Applications Auto transformer tap changing is a practical method of adjusting transformer output voltage without unnecessarily interrupting the electrical supply. In power transmission and distribution networks, the load does not remain constant throughout the day. As load current changes, voltage drops across transformers, cables, feeders, and transmission lines also change. A tap-changing arrangement compensates for these variations by modifying the effective number of turns in the transformer winding. A reactor-type on-load tap changer uses a center-tapped reactor, selector switches, and a bypass or short-circuiting switch to transfer the load from one tap to the next. The reactor limits the circulating current during the transition, allowing the tap position to change while the transformer continues supplying the connected load. This article explains the auto transformer tap-changing working principle , switch...

PLUG REVERSING OF CAPACITOR START MOTORS

The capacitor start motors suffer from the disadvantage that they are not easily reversible due to the centrifugal switch connected in the auxiliary winding. The motor cannot be instantaneously reversed by simple control as the auxiliary winding remains disconnected till the motor comes near to zero speed. However, by proper design of the control circuit the motor can be made instantly reversible. This is accomplished by using an electromagnetic relay along with a special two contact centrifugal switch as shown in Figure. The circuit shown in Figure is for a small hoist using a capacitor start motor. The upper and lower limits of travel are controlled by two limit switches viz. LSU and LSD. When UP-push button is pressed, contactor U gets energized. Its contacts U 1  and U 2  energies the main winding. Closing of its contact U 3  causes relay R to get energized through the centrifugal switch contacts A—B. After the energization of relay R auxiliary winding gets ene...

COMPONENTS OF HIGH VOLTAGE DC TRANSMISSION SYSTEM

Figure: A schematic of a bipolar HVDC system identifying main components

BENEFITS OF UTILIZING FACTS DEVICES

The advantages of using FACTS devices in electrical transmission systems are described below. 1. MORE UTILIZATION OF EXISTING TRANSMISSION SYSTEM In all the countries, the power demand is increasing day by day to transfer the electrical power and controlling the load flow of the transmission system is very necessary this can be achieved by more load centers which can change frequently. Addition of new transmission line is very costly to take the increased load on the system; in that case FACTS devices are much economical to meet the increased load on the same transmission lines. 2. MORE INCREASED TRANSIENT AND DYNAMIC STABILITY OF THE SYSTEM The Long transmission lines are inter-connected with grids to absorb the changing the loading of the transmission line and it is also seen that there should be no line fault creates in the line / transmission system. By doing this the power flow is reduced and transmission line can be trip. By the use of FACTS devices high power t...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Reversing the Direction of a Universal Motor: Methods and Circuit Diagram

How to Reverse the Direction of Rotation of a Universal Motor Introduction A universal motor is a high-speed electric motor that can operate on either an alternating-current or direct-current supply when designed for the applicable voltage and frequency. It is widely used in portable electric drills, grinders, vacuum cleaners, mixers, sewing machines, small machine tools, and other equipment requiring high starting torque and compact construction. The direction of rotation of a universal motor can be changed by reversing the direction of current through either the armature winding or the field winding relative to the other. The current must be reversed in only one of these windings. If the connections of both windings are reversed simultaneously, the relative direction of the field flux and armature current remains unchanged, and the motor continues rotating in the same direction. Before studying the reversing methods, readers may review the Universal Series Motors Electric Motors and...

SPEED CONTROL OF UNIVERSAL MOTOR

There are various methods of controlling the speed of a universal motor. A wide range of speed control is possible by inserting a rheostat in the line circuit which causes variable voltage to appear across the motor terminals resulting in reduced motor speed. Another method of speed control, not very commonly used is by brush shifting mechanism. The speed of the motor increases when the brushes are moved backward relative to the direction of rotation. However, only a limited range of speed control is possible by this method. This is because when the brushes are moved further from the magnetic neutral, commutation worsens. Another speed control method makes use of a tapped field winding. Universal motors are always bipolar. The number of turns on the two poles need not always be the same as the air gap flux is created by series combination of mmfs of the two pole windings. As shown in Figure 1 the field winding having larger number of turns is tapped at three points thus making p...