SURFACE BREAKDOWN

Surface flashover

Surface flashover is a breakdown of the medium in which the solid is immersed. The role of the solid dielectric is only to distort the field so that the electric strength of the gas is exceeded.

If a piece of solid insulation is inserted in a gas so that the solid surface is perpendicular to the equipotentials at all points, then the voltage gradient is not affected by the solid insulation. An example of this is a cylindrical insulator placed in the direction of a uniform field. Field intensification results if solid insulation departs even in detail from the cylindrical shape. In particular if the edges are chipped, or if the ends of the cylinder are not quite perpendicular to the axis, then an air gap exists next to the electrode, and the stress can reach up to 0r times the mean stress in the gap. Discharge may therefore occur at a voltage approaching 1/0r times the breakdown voltage in the absence of the cylinder, and these discharges can precipitate a breakdown.

The three essential components of the surface flashover phenomena are

(a) The presence of a conducting film across the surface of the insulation

(b) A mechanism whereby the leakage current through the conducting film is interrupted with the production of sparks,

(c) Degradation of the insulation must be caused by the sparks.

The conducting film is usually moisture from the atmosphere absorbed by some form of contamination. Moisture is not essential as a conducting path can also arise from metal dust due to wear and tear of moving parts. Sparks are drawn between moisture films, separated by drying of the surface due to heating effect of leakage current, which act as extensions to the electrodes. {For a discharge to occur there must be a voltage at least equal to the Paschen minimum for the particular state of the gas. For example, Paschen minimum in air at N.T.P it is 380 V, whereas tracking can occur at well below 100 V. It does not depend on gaseous breakdown.] Degradation of the insulation is almost exclusively the result of heat from the sparks, and this heat either carbonizes if tracking is to occur, or volatilizes if erosion is to occur. Carbonization results in a permanent extension of the electrodes and usually takes the form of a dendrite growth. Increase of creep age path during design will prevent tracking, but in most practical cases, moisture films can eliminate the designed creep age path.

Tracking

Tracking is the formation of a permanent conducting path across a surface of the insulation, and in most cases the conduction (carbon path) results from degradation of the insulation itself leading to a bridge between the electrodes.

The insulating material must be organic in nature for tracking to occur.

Erosion

In a surface discharge, if the products of decomposition are volatile and there is no residual conducting carbon on the surface, the process is simply one of pitting. This is erosion, which again occurs in organic materials.

If surface discharges are likely to occur, it is preferable to use materials with erosion properties rather than tracking properties, as tracking makes insulation immediately completely ineffective, whereas erosion only weakens the material but allows operation until replacement can be made later.

Comments

Popular posts from this blog

ADVANTAGES AND DISADVANTAGES OF CORONA

Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. ADVANTAGES (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. DIS-ADVANTAGES (i) Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines.

ADVANTAGES OF PER UNIT SYSTEM

PER UNIT SYSTEM The per-unit system expressed the voltages, currents, powers, impedances, and other electrical quantities basis by the equation: Quantity per unit (pu) = Actual value/ Base value of quantity ADVANTAGES OF PER UNIT SYSTEM While performing calculations, referring quantities from one side of the transformer to the other side serious errors may be committed. This can be avoided by using per unit system. Voltages, currents and impedances expressed in per unit do not change when they are referred from one side of transformer to the other side. This is a great advantage. Per unit impedances of electrical equipment of similar type usually lie within a narrow range, when the equipment ratings are used as base values. Transformer connections do not affect the per unit values. Manufacturers usually specify the impedances of machines and transformers in per unit or percent of name plate ratings. Transformers can be replaced by their equivalent series impedances. ...

ABSOLUTE AND SECONDARY INSTRUMENTS

The various electrical instruments may, in a very broad sense, be divided into (i) Absolute Instruments (ii) Secondary Instruments. Absolute Instruments are those which give the value of the quantity to be measured, in terms of the constants of the instrument and their deflection only. No previous calibration or comparison is necessary in their case. The example of such an instrument is tangent galvanometer, which gives the value of current, in terms of the tangent of deflection produced by the current, the radius and number of turns of wire used and the horizontal component of earth’s field.  Secondary Instruments  are those, in which the value of electrical quantity to be measured can be determined from the deflection of the instruments, only when they have been pre-calibrated by comparison with an absolute instrument. Without calibration, the deflection of such instruments is meaningless. It is the secondary instruments, which are most generally used in ev...