Skip to main content

MUTUAL INDUCTANCE

Suppose we hook up an AC generator to a solenoid so that the wire in the solenoid carries AC. Call this solenoid the primary coil. Next place a second solenoid connected to an AC voltmeter near the primary coil so that it is coaxial with the primary coil. Call this second solenoid the secondary coil. As shown in figure.

The alternating current in the primary coil produces an alternating magnetic field whose lines of flux link the secondary coil (like thread passing through the eye of a needle). Hence the secondary coil encloses a changing magnetic field. By Faraday’s law of induction this changing magnetic flux induces an emf in the secondary coil. This effect in which changing current in one circuit induces an emf in another circuit is called mutual induction.

Let the primary coil have N1 turns and the secondary coil have N2 turns. Assume that the same amount of magnetic flux F2from the primary coil links each turn of the secondary coil. The net flux linking the secondary coil is then N2F2. This net flux is proportional to the magnetic field, which, in turn, is proportional to the current I1 in the primary coil. Thus we can write N2F2µI1. This proportionality can be turned into an equation by introducing a constant. Call this constant M, the mutual inductance of the two coils:

The unit of inductance is WB/A=Henry (H) named after Joseph Henry.

The emf induced in the secondary coil may now be calculated using Faraday’s law:


The above formula is the emf due to mutual induction.

Example

The apparatus used in Experiment EM-11B consists of two coaxial solenoids. A solenoid is essentially just a coil of wire. For a long, tightly-wound solenoid of n turns per unit length carrying current I the magnetic field over its cross-section is nearly constant and given by. Assume that the two solenoids have the same cross-sectional area A. Find a formula for the mutual inductance of the solenoids.

Comments

Popular posts from this blog

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PRINCIPLE OF OPERATION OF UNIFIED POWER FLOW CONTROLLER UPFC

UPFC consist of two back to back converters named VSC1 and VSC2, are operated from a DC link provided by a dc storage capacitor. These arrangements operate as an ideal ac to ac converter in which the real power can freely flow either in direction between the ac terminals of the two converts and each converter can independently generate or absorb reactive power as its own ac output terminal. Figure: Basic UPFC scheme One VSC is connected to in shunt to the transmission line via a shunt transformer and other one is connected in series through a series transformer. The DC terminal of two VSCs is coupled and this creates a path for active power exchange between the converters. VSC provide the main function of UPFC by injecting a voltage with controllable magnitude and phase angle in series with the line via an injection transformer. This injected voltage act as a synchronous ac voltage source. The transmission line current flows through this voltage source resulting in reactive an...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

CLASSIFICATION OF HVDC LINKS

HVDC links may be broadly classified into the following categories: Monopolar Links Bipolar Links Homopolar Links The basic configuration of a monopolar link is shown in figure. It uses one conductor, usually of negative polarity. The return path is provided by ground or water. Cost considerations often lead to the use of such systems, particularly for cable transmission. This type of configuration may also be the first stage in the development of a bipolar system. Instead of ground return, a metallic return may be used in situation where the earth resistivity is too high or possible interference with underground/ under water metallic structures is objectionable. The conductor forming the metallic return is at low voltage.

ELEMENTS OF MEASUREMENT SYSTEM

I) PRIMARY SENSING ELEMENT This is the element that first receives energy from the measured medium and procedures an output depending on some way on the measured quantity (measured).  The output is some physical variable e.g. displacement or voltage. An instrument always extract some energy from the measured medium. The measured quantity is always disturbed by the act of measurement, which makes a perfect theoretically impossible. Good instruments are designed to minimize this loading effect.  II) VARIABLE CONVERSION ELEMENT If may be necessary to convert the output signal of the primary sensing element to another more suitable variable while preserving the information content of the original signal. This element performs this function.  III) VARIABLE MANIPULATION ELEMENT An instrument may require that a signal represented by some physical variable be manipulated by some way.  By manipulation we mean specifically a change in numerical ...