Skip to main content

METHODS OF STARTING INDUCTION MOTORS

When the maximum kW rating of an induction motor is reached for direct-on-line starting, it becomes necessary to introduce an alternative method of starting the motor. There are several methods used in the oil industry. The object is to reduce the starting current drawn from the supply during all or part of the run-up period. There are two basic approaches that can be used:-

• Select special-purpose designs for the motor in which the winding arrangements are modified by external switching devices that are matched to the motor, e.g. star-delta motor and starter.

• Select conventional motors but use special external starting devices, e.g. Korndorfer starter, autotransformer starter, ‘soft-starter’ using a controlled rectifier-inverter system.

In all cases of reduced voltage starting, care must be taken to check that the motor will create sufficient torque at the reduced voltage to accelerate the load to the desired speed in as short a time as possible. Excessive run-up times must be avoided as. When the run-up time is expected to be high the manufacturer of the motor should be consulted regarding the possibility of damage and infringement of its guarantees. The following methods are the most commonly used, typically in the order shown below.

• Star-delta method.
• Korndorfer auto-transformer method.
• Soft-start power electronics method.
• Series reactor method.
• Part winding method.

Star-Delta Method Of Starting Induction Motors

A specially designed motor is used. The stator windings are arranged so that the start and finish of each phase winding in the stator is brought out to the main terminal box so that six terminals are available for connection to cables. Usually two three-core or four-core cables are used unless their conductor size becomes too large, in which case single-core cables would be used. The windings are connected externally in star for starting and delta for running. The external connections are made by using a special starter in the motor control centre which also provides control relays and current transformers that determine when the transfer from star to delta should take place.

Disadvantages of Star-Delta Method

• The windings are open-circuited during the transfer and this is not considered good practice, a delay should be incorporated to allow the flux in the motor to decay during the transfer.

• The starting current and torque are reduced to 33% of their value during the run-up period. This reduction may be too much for some applications.

• The running condition requires a delta winding connection and this has the disadvantage that harmonic currents can circulate in the windings.

Figure shows the basic circuit for a star-delta starter.



Korndorfer Auto-Transformer Method Of Starting Induction Motors

A standard design of motor is used. An external auto-transformer is connected between the main circuit breaker, or contactor, and the motor during the starting and run-up period. Figure 5.8 shows the connections that are commonly used in a balanced three-phase arrangement. The voltage ratio of the auto-transformer needs to be carefully selected. If it is too high then the full benefit is not achieved. If too low then insufficient torque will be created. The most effective ratio is usually found between 65% and 80%.

Disadvantage of Korndorfer Auto-Transformer Method

Two extra three-phase circuit breakers or contactors are necessary, thus making three in total for the motor circuit, which require space to be allocated. Retro-fitting a Korndorfer starter may therefore be difficult if space is scarce.

Figure shows the basic circuit for Korndorfer Auto-Transformer Method.



Soft-Start Power Electronics Method Of Starting Induction Motors

A standard design of motor is used. An external rectifier-inverter is connected between the main circuit breaker, or contactor, and the motor during the starting and run-up period. The starter varies the frequency and voltage magnitude of the applied three-phase supply to the motor. Upon starting the frequency and voltage are set to their lowest values, and thereafter they are slowly raised as the shaft speed increases. The intent is to operate the motor in its near-synchronous speed state for each frequency that the motor receives.

The rectifier-inverter equipment is expensive when compared with other switching and transformer methods, but it has several advantages:-

• The starting current can be limited to a value that is equal to or a little higher than the full-load current of the motor.

• The torque created in the motor during the whole run-up period can be in the order of the full-load value, and so the shape of the inherent torque-speed curve of the motor is not a critical issue for most standard designs of motors.

Series Reactor Method Of Starting Induction Motors

A standard design of motor is used. This is a simple method that requires the insertion of a series reactor during starting. The reactor is bypassed once the motor reaches its normal working speed.

Only one extra circuit breaker or contactor is required. The amount of reactance is calculated on the basis of the desired reduction of line current during starting, but the limiting factor is the reduced starting torque. The torque is reduced for two reasons, firstly because the total circuit impedance is increased and secondly the reactance-to-resistance ratio is increased.

Part Winding Method Of Starting Induction Motors

A special design of motor is used. The stator has two three-phase windings that are arranged in parallel and wound in the same slots. If the two windings are the same then on starting and during run-up one winding would provide half of the total torque at any speed. Hence one winding is used for starting and both for running. The method is not suited to small or high speed motors. With two equal windings the starting current and torque are half of their totals. This method is seldom used in the oil industry because of the preference for standard motors, and the availability of satisfactory alternative methods.

Comments

Unknown said…
hi i have a motor 750 hp can i used this method with this type of drawing (auto transformer )without any kind of restrectins or resk ,my mail is mohamed_alanany2003@yahoo.com .thanks

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

CLASSIFICATION OF POWER SYSTEM BUSES

Each bus in the system has four variables: voltage magnitude, voltage angle, real power and reactive power. During the operation of the power system, each bus has two known variables and two unknowns. Generally, the bus must be classified as one of the following bus types: 1. SLACK OR SWING BUS This bus is considered as the reference bus. It must be connected to a generator of high rating relative to the other generators. During the operation, the voltage of this bus is always specified and remains constant in magnitude and angle. In addition to the generation assigned to it according to economic operation, this bus is responsible for supplying the losses of the system. 2. GENERATOR OR VOLTAGE CONTROLLED BUS During the operation the voltage magnitude at this the bus is kept constant. Also, the active power supplied is kept constant at the value that satisfies the economic operation of the system. Most probably, this bus is connected to a generator where the voltage i...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

DIFFERENCE BETWEEN GRID STATION AND SUB STATION

An electrical power substation is a conversion point between transmission level voltages (such as 138 KV) and distribution level voltages (such as 11 KV). A substation has one or more step-down transformers and serves a regional area such as part of a city or neighborhood. Substations are connected to each other by the transmission ring circuit. An electrical grid station is an interconnection point between two transmission ring circuits, often between two geographic regions. They might have a transformer, depending on the possibly different voltages, so that the voltage levels can be adjusted as needed. The interconnected network of grid stations is called the grid, and may ultimately represent an entire multi-state region. In this configuration, loss of a small section, such as loss of a power station, does not impact the grid as a whole, nor does it impact the more localized neighborhoods, as the grid simply shifts its power flow to compensate, giving the power station o...